ENERIUM 100 CFG

Highlights
  • Communication: Ethernet (RJ45) or Modbus RS485 + up to 8 on-off I/Os, 8 analog inputs and 4 analog outputs + USB on front panel
  • Accuracy class 0.5 (IEC 61557-12)
  • 4 trend curves (instantaneous or average values ) on all electrical quantities and analog signals
  • 16 programmable alarms
  • Time/date-stamped alarms log: up to 64 events
  • Possibility of 24/48VDC auxiliary power supply
Description
The ENERIUM100 power monitor can be used to monitor electrical installations by implementing trend curves triggered by alarms on the electrical quantities or the signals. The built-in Modbus RS485 or Ethernet output enables remote use and operation of the product, its on-off or analog inputs/outputs mean it can interface very simply with supervision or control architectures.

Main specifications of the instrument:

  • Active energy accuracy class: 0.5s (EN 62053-22) / 0.5 (IEC 61557-12)
  • Measurement accuracy:  Voltage 0.2 % (from 20 % to 130 %) / Current: 0.2 % (from 10 % to 130 %)
  • Max. measured power: 2 GW (VT ≤ 650 kV primary / CT ≤ 25 kA primary)
  • Measurement on all 4 quadrants (Import / Export)
  • Measurement on single and three-phase networks (3/4 wires, balanced / unbalanced)
  • Measurement functions (see detailed table): instantaneous (1 sec.), average (programmable), min., max., min. of averages, max. of averages
  • Measurement of harmonics up to the 25th order(with graphical representation per order) and THD-U / V / I / In
  • Hour meters: 3 (network presence, load presence, aux. source)
  • Number of on-off inputs/outputs: 2 outputs configurable in pulse or alarm mode and 2 inputs
  • Customizable graphical screen (up to 3 as required) with Fresnel diagram representation and gauges (V, U, I, P), as well as display in harmonic-order histograms
  • 16 configurable alarms and time/date-stamped Recordings of up to 64 events
  • Number of on-off or analog I/Os: Up to 8 on-off inputs or outputs (configurable in pulse or alarm mode), up to 8 analog inputs or 4 analog outputs
  • Metrological LED
  • 4 trend curves triggered on instantaneous or average values of the electrical parameters or the analog inputs
  • Mounting: on front panel or DIN rail
  • Configuration of all the parameters: on front panel (USB link) or using remote communication
  • Possibility of upgrading the firmware on front panel or remotely
  • Indication of connection errors
  • Auxiliary power supply: 80 to 265 Vac from 42.5 to 69 Hz / 110 to 375 Vdc / 19 to 58 Vdc
  • Operating temperature: -10° C to +55° C (K55 as per IEC 61557-12)
Other specifications: see detailed technical documentation



The power monitors in the ENERIUM range are specially designed for energy management and energy efficiency.  With their advanced measuring functions, they can be used to analyze energy quality, correlate climate data with energy consumption or alert the user when consumption exceeds the threshold.

The power monitors in the ENERIUM range offer a wide variety of functions and configurability, but the 6 models in the range share the following essential features:

  • RS485 or Ethernet communication as standard
    Management of the configurable alarms and triggers on measured quantities or Inputs-Outputs
    Compliance with the central IEC61557-12 standard
    Ergonomic display
    Made in France

The Power Monitors selection guide is an essential tool for targeting the power monitor you need for your application.

Further information available on the website dedicated to the power monitors from Chauvin Arnoux Energy: http://www.enerium.enerdis.com/

Designation
Price
Reference
Quantity
Actions
ENERIUM100
-
ENERIUM100-CFG
-
Close

Informations produit

Informations utilisateur

Adresse

  • For further information, please see our policy on confidentiality.

* Required Fields